A – data types, Supported data types, When using array variables – Rockwell Automation 2080-LC50 Micro800 Programmable Controllers: Getting Started with PanelView Plus User Manual
Page 59: When using array, Data types, Appendix
Rockwell Automation Publication 2080-QS003A-EN-E - September 2014
59
Appendix
A
Data Types
Supported Data Types
The following data types are supported.
When you see the controller variables in PanelView Plus, it will be shown as
described in the table below.
Structured data types are NOT supported.
When Using Array
Variables
A variable can be created as an array of data types and up to three dimensions are
supported. The following rules must be observed when using an array of data
types.
1.
An array cannot be a Boolean data type.
2.
An array cannot be an Array data type.
Data Type
Hex Value
Dec Value
Description
BOOL
0xC1
193
Logical Boolean with values TRUE(1) and FALSE(0)
SINT
0xC2
194
Signed 8-bit integer value.
INT
0xC3
195
Signed 16-bit integer value.
DINT
0xC4
196
Signed 32-bit integer value.
LINT
(1)
(1) LINT data types are not fully supported in PanelView Plus. When using LINT tags, values that are less than 53
bits are not displayed correctly or may appear wireframed on the display client.
0xC5
197
Signed 64-bit integer value.
USINT
0xC6
198
Unsigned 8-bit integer value.
UINT
0xC7
199
Unsigned 16-bit integer value.
UDINT
0xC8
200
Unsigned 32-bit integer value.
ULINT
0xC9
201
Unsigned 64-bit integer value.
REAL
0xCA
202
32-bit floating point value.
LREAL
0xCB
203
64-bit floating point value.
STRING
(2)
(2) The STRING data type does not support Unicode.
0xDA
218
Character string.
Data Type (Micro800)
Appears as Data Type (PanelView Plus)
BYTE
USINT
WORD
UINT
DWORD
UDINT
LWORD
ULINT