Iam input connector pinouts, Iam /am motor power and brake connector pinouts – Rockwell Automation 2094-BMxx-M Kinetix 6200 and Kinetix 6500 IAM and AM Power Modules Installation Instructions User Manual
Page 14

14 Kinetix 6200 and Kinetix 6500 IAM and AM Power Modules
Rockwell Automation Publication 2094-IN011D-EN-P - August 2013
IAM Input Connector Pinouts
Control Power Connector
DC Bus and Input Power Connector
Contactor Enable Connector
IAM /AM Motor Power and Brake Connector Pinouts
Motor Power Connector
CPD Pin
Description
Signal
1
Control power VAC input
CTRL 2
2
CTRL 1
IPD Pin
Description
Signal
1
An integral, unregulated power supply, consisting of AC line input, three-phase bridge
rectifier, and filter capacitors
DC-
2
DC+
3
Chassis ground
4
Three-phase input power
L3
5
L2
6
L1
CED Pin
Description
Signal
1
Relay-driven dry contact used in the safety string for a three-phase power contactor
CONT EN-
2
CONT EN+
MP Pin
Description
Signal
4
Chassis ground
3
Three-phase motor power
W
2
V
1
U
IMPORTANT
To meet CE requirements, combined motor-power cable length for all axes on the same DC bus
must not exceed 240 m (787 ft) with 460V systems. Drive-to-motor power cables must not
exceed 90 m (295.5 ft).