Plc-5 channel 0 simplex example – Rockwell Automation 2706-F11J_F11JC_F21J_F21JC DL50 INSTALLATION MANUAL User Manual
Page 82
Chapter 6
Slave Mode Operation / Examples
6–18
PLC-5 Channel 0 Simplex Example
This example demonstrates how to use the RS232 Channel 0 of supporting
members of the Allen-Bradley PLC-5 family to trigger a Dataliner DL50
display. In the example, a counter is used to simulate changing variable data,
which could be a motor speed or a temperature. This will demonstrate how
variable data may be incorporated into messages.
The program below will display the message “Temp ##” in green (red on
F11J or F21J), where ## represents the sample variable. The text size will
depend on the character size setting on the DL50 display.
Temp ##
Channel 0 Configuration
The first step is to configure the PLC channel 0 port to communicate with a
DL50 slave. Table 6.C shows the user mode configuration of the PLC
channel 0. Note that the baud rate should match that being used by the DL50.
Table 6.C
Configuring the Channel 0 Port
Channel 0
Channel 1A
Channel 1B
Channel 2A
Channel 2B
Channel 3A
DH+
SCANNER MODE
USER
ADAPTER MODE
N/A
SCANNER MODE
User Mode
Channel 0 Configuration
Diag.file:
Remote mode change:
Mode Attention Char.:
Baud rate:
Stop bits:
Control line:
Echo/delete mode:
Termination 1:
Termination 2:
N11
DISABLED
\0x1b
9600
1
NO HANDSHAKING
CRT
\0xd
\0x0
XON/XOFF:
DISABLED
System mode char.:
S
User mode char.:
U
Parity:
NONE
Bits per character:
8
RTS send delay (20 ms):
0
RTS off delay (20 ms):
Append 1:
\0xd
0
Append 2:
0