3–23
Addressing Modes for Your Remote I/O
Publication 1771-UM001A-US-P - February 2000
Follow these guidelines when you select 1/2-slot addressing:
•
Place input modules opposite output modules; place output
modules opposite input modules.
•
You can use 8, 16 and 32-point I/O modules.
•
Output modules placed opposite output modules reflect the same
bits in the output image table.
You can use block-transfer modules in a complementary I/O
configuration with 1/2-slot addressing. Use block-transfer modules
with these guidelines:
•
When using double-slot block-transfer modules in the primary
chassis:
–
The left-most slot of the two corresponding I/O slots in the
complementary chassis must be empty.
–
You can place any single-slot I/O module in the right slot
of the two corresponding I/O slots of the complementary
chassis
•
When using single-slot block-transfer modules, the
corresponding I/O slot in the complementary chassis must be
left empty.
You can have a mix of 1-slot and 2-slot addressing in individual
chassis assigned one I/O rack number (with up to eight I/O groups).
For example: you can select 2-slot addressing for a 1771-A2B I/O
chassis and 1-slot addressing for a 1771-A1B chassis to make up one
assigned I/O rack number (Figure 3.20).
Figure 3.20
Mixing Addressing Methods in Chassis Assigned One I/O
Rack Number
13126
1771ĆA1B I/O Chassis
using 1Ćslot addressing
1771ĆA2B I/O Chassis
using 2Ćslot addressing
One Assigned I/O Rack Number
1
2
3
4-5
6-7
0
Mixing 1 and 2ĆSlot
Addressing in Individual
Chassis