Rockwell Automation 1771-ASB/E Remote I/O Adapter User Manual User Manual
Page 20
2–6
Installing Your Module
Publication 1771-UM001A-US-P - February 2000
Figure 2.5
Module Switch Assembly Settings for PLCĆ3 Family
Processors
1 2 3 4 5 6 7 8
First I/O group number
(Table 2.B)
I/O rack number
(Table 2.B)
Address Switch Assembly
(S1)
Switch Assembly (S2)
Pressed in at top
(ON)
Pressed in at bottom
(OFF)
1 2 3 4
5 6
Switch Position
1
2
57.6K Baud Ć 10,000ft
115.2K Baud Ć 5,000ft
Not Used
Maximum I/O
chassis distance
Link Response Ć ON for series B emulation
Scan Ć ON for all but last 4 slots
OFF for all slots
OFF for unrestricted
Always OFF
10799ĆI
ATTENTION: Link response switch must
be ON when using the following scanner
modules:
1775ĆS4A
1775ĆS4B
1775ĆS5
1775ĆSR5
1775ĆSR
ON
OFF
OFF
OFF
ON
ON
ON
230.4K Baud Ć 2,500ft
1
OFF
1 230.4K Baud with 1775ĆS5 revision A/G, and
1775ĆSR5 revision A/G scanners only.
Off
(ON)
(OFF)
(ON)
(OFF)
OPEN
OPEN
Table 2.B
I/O Rack Switch Selections for the Address Switch
Assembly (PLCĆ3 Family Processors)
Rack
#
Switch Setting
1
2
3
4
5
6
Rack
#
Switch Setting
1
2
3
4
5
6
Rack
#
Switch Setting
1
2
3
4
5
6
Rack
#
Switch Setting
1
2
3
4
5
6
00
On On On On On On
20
On Off On On On On
40
Off On On On On On
60
Off Off On On On On
01
On On On On On Off
21
On Off On On On Off
41
Off On On On On Off
61
Off Off On On On Off
02
On On On On Off On
22
On Off On On Off On
42
Off On On On Off On
62
Off Off On On Off On
03
On On On On Off Off
23
On Off On On Off Off
43
Off On On On Off Off
63
Off Off On On Off Off
04
On On On Off On On
24
On Off On Off On On
44
Of On On Off On On
64
Off Off On Off On On
05
On On On Off On Off
25
On Off On Off On Off
45
Off On On Off On Off
65
Off Off On Off On Off
06
On On On Off Off On
26
On Off On Off Off On
46
Off On On Off Off On
66
Off Off On Off Off On
07
On On On Off Off Off
27
On Off On Off Off Off
47
Off On On Off Off Off
67
Off Off On Off Off Off
10
On On Off On On On
30
On Off Off On On On
50
Off On Off On On On
70
Off Off Off On On On
11
On On Off On On Off
31
On Off Off On On Off
51
Off On Off On On Off
71
Off Off Off On On Off
12
On On Off On Off On
32
On Off Off On Off On
52
Off On Off On Off On
72
Off Off Off On Off On
13
On On Off On Off Off
33
On Off Off On Off Off
53
Off On Off On Off Off
73
Off Off Off On Off Off
14
On On Off Off On On
34
On Off Off Off On On
54
Off On Off Off On On
74
Off Off Off Off On On
15
On On Off Off On Off
35
On Off Off Off On Off
55
Off On Off Off On Off
75
Off Off Off Off On Off
16
On On Off Off Off On
36
On Off Off Off Off On
56
Off On Off Off Off On
76
Off Off Off Off Off On
17
On On Off Off Off Off
37
On Off Off Off Off Off
57
Off On Off Off Off Off
77
Not valid
1st I/O Group
Number
Switch Selections
7
8
Note:
Rack address 77 is an illegal configuration.
PLCĆ3 processors can scan racks 0Ć76.
0
On
On
2
On
Off
4
Off
On
6
Off
Off