Rockwell Automation 1771-ASB/E Remote I/O Adapter User Manual User Manual
Page 21
2–7
Installing Your Module
Publication 1771-UM001A-US-P - February 2000
Figure 2.6
Module Switch Assembly Settings for PLCĆ5 Family, SLC
and ControlLogix Processors Without Complementary I/O
1 2 3 4 5 6 7 8
First I/O group number
(Table 2.C)
I/O rack number
(Table 2.C)
Address Switch Assembly
(S1)
Switch Assembly
(S2)
1 2 3 4
5 6
Link Response Ć ON for series B emulation
OFF for unrestricted
Scan Ć ON for all but last 4 slots
OFF for all slots
Always OFF
10800ĆI
Switch Position
1
2
ON OFF 57.6K Baud Ć 10,000ft
OFF OFF 115.2K Baud Ć 5,000ft
ON ON
Not Used
Maximum I/O
chassis distance (see note)
OFF ON
230.4K Baud Ć 2,500ft
Note: PLCĆ5/15 and 5/25 processors operate
at 57.6K baud only.
Pressed in at top
(ON)
Pressed in at bottom
(OFF)
Off
(ON)
(OFF)
(ON)
(OFF)
OPEN
OPEN
Table 2.C
I/O Rack Selection for PLCĆ5 Family Processors
without Complementary I/O
Rack
#
Switch Setting
1
2
3
4
5
6
Rack
#
Switch Setting
1
2
3
4
5
6
1st I/O
Group
Number
Switch
Selections
7
8
00
On On On On On On
20
On Off On On On On
0
On
On
01
On On On On On Off
21
On Off On On On Off
2
On
Off
02
On On On On Off On
22
On Off On On Off On
4
Off
On
03
On On On On Off Off
23
On Off On On Off Off
6
Off
Off
04
On On On Off On On
24
On Off On Off On On
05
On On On Off On Off
25
On Off On Off On Off
06
On On On Off Off On
26
On Off On Off Off On
07
On On On Off Off Off
27
On Off On Off Off Off
10
On On Off On On On
30
On Off Off On On On
11
On On Off On On Off
31
On Off Off On On Off
12
On On Off On Off On
32
On Off Off On Off On
13
On On Off On Off Off
33
On Off Off On Off Off
14
On On Off Off On On
34
On Off Off Off On On
15
On On Off Off On Off
35
On Off Off Off On Off
16
On On Off Off Off On
36
On Off Off Off Off On
17
On On Off Off Off Off
37
On Off Off Off Off Off
PLCĆ5/11 processors can scan rack 03.
PLCĆ5/15 and PLCĆ5/20 processors can scan racks 01Ć03.
PLCĆ5/25 and PLCĆ5/30 processors can scan racks 01Ć07.
PLCĆ5/40 and PLCĆ5/40L processors can scan racks 01Ć17.
PLCĆ5/60 and PLCĆ5/60L processors can scan racks 01Ć27.
PLCĆ5/250 processors can scan racks 0Ć37.