Troubleshoot with the Indicators

This module has the following indicators:

Network and Module status indicator

Logic status indicator

Auxiliary Power indicator

Individual I/O status indicators for inputs 0 through 3 and
outputs 0 through 3.

The following table describes network and module status indicators.

Net/Mod Status Indicator

Indicator

Status

Off

No power or auto bauding

Flashing Green/Off

On line but not connected

Solid Green

On line, link OK, connected

Flashing Red

Recoverable fault - module configuration error

I/O connection fault - one or more I/O connections in the timed-out
state