Rockwell Automation 1792D-4BV4D ArmorBlock MaXum 4 Input/4 Output Module with 8 Connectors, Series B I.I. User Manual
Installation instructions
1
Publication 1792D-IN050A-EN-P - February 2001
Installation Instructions
ArmorBlock MaXum 4 Input / 4 Output
Module with 8 Connectors, Series B
(Cat. No. 1792D-4BV4D)
This ArmorBlock MaXum
I/O module (Cat. No. 1792D-4BV4D) is a
stand-alone 24V dc I/O product which communicates via a
DeviceNet
network. The sealed housing of this module requires no
enclosure.
This model has 4 inputs and 4 outputs with 8 connectors. Inputs are
24V dc automatically configured for PNP (sourcing) or NPN (sinking)
devices. Four self-protected 24V dc outputs can provide up to 0.5
amp each. Diagnostic features are short circuit, open wire, and no
load detection reported to the point level. Local logic control has
been added to this Series B product. The 1792D-4BVT4D also has 4
inputs and 4 outputs, but only 4 connectors. This new module gives
you complete single point diagnostics.
42758
Document Outline
- ArmorBlock MaXum 4 Input / 4 Output Module with 8 Connectors, Series B
- Package Contents
- European Union Directive Compliance
- Install Your ArmorBlock MaXum I/O Module
- Set the Node Address
- Install the Module
- Connect the Input / Output Cord Sets to the MaXum Module
- Output Power and DeviceNet Cables
- Communicate With Your ArmorBlock MaXum I/O Module
- Troubleshoot with the Indicators
- Hazardous Location Approval
- Back Cover