Publication 1792D-IN050A-EN-P - February 2001

Refer to the table below for the word/bit definitions.

The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our web site at
http://www.ab.com/networks for producer/consumer technology
information and updates.

Bit

07

06

05

04

03

02

01

00

Produced
Byte 0

ISC-D

ISC-C

ISC-B

ISC-A

I3

I2

I1

I0

Produced
Byte 1

OFLT3

OFLT2

OFLT1

OFLT0

OW-D

OW-C

OW-B

OW-A

Produced
Byte 2

RSVD

OPWR

RSVD

RSVD

RSVD

RSVD

RSVD

RSVD

Consumes
Byte 0

RSVD

RSVD

RSVD

RSVD

O3

O2

O1

O0

Where: ISC=Input Short Circuit in Sensor Source Voltage; I = Input; OFLT = Output fault;
OW= Off Wire; RSVD = Reserved; OPWR= Output Power (Auxiliary Power); O = Output

Byte

Bit

Description

Produces 0

00-03

04-07

Input Status bits: When the bit is set (1), the input is on.
Bit 00 = to input 0, bit 01 = to input 1, bit 02 = to input 2, bit
03 = to input 3.
Input short circuit fault: ISC-A = a short circuit for connector A
Input short circuit fault: ISC-B = a short circuit for connector B
Input short circuit fault: ISC-C = a short circuit for connector C
Input short circuit fault: ISC-D = a short circuit for connector D

Produces 1

00-03

04-07

Input off wire fault: OW-A = an off-wire fault for connector A
Input off wire fault: OW-B = an off-wire fault for connector B
Input off wire fault: OW-C = an off-wire fault for connector C
Input off wire fault: OW-D = an off-wire fault for connector D
Output no load or overload fault (OFLT): - When the bit is set
(1) an output fault has occurred. OFLT0 = output 0,
OFLT1 = output 1, OFLT2 corresponds to output 2,
OFLT3 = output 3.

Produces 2

00-05
06

07

RSVD = Reserved
Output Power Fault (OPWR): When the bit is set (1) Auxiliary
Power is not present.
RSVD = Reserved

Consumes 0

00-03

04-07

Output bits: When the bit is set (1), the output will be turned
on. Bit 00 corresponds to output O0, bit 01 corresponds to
output 01, bit 02 to output 02, bit 03 to output 03.