Rockwell Automation 1769-OF4VI CompactLogix Module User Manual
Page 24

24 Compact 1769-OF4VI Isolated Analog Output Module
Rockwell Automation Publication 1769-IN076B-EN-P - August 2010
Specification
1769-OF4VI
Accuracy Drift with Temperature
±0.0086% FS per °C
Output Ripple
(1)
range 0 to 50 kHz
(referred to output range)
±0.05%
Non-linearity (in percent full scale)
±0.05%
Repeatability
(2)
(in percent full scale)
±0.05%
Output Error Over Full Temperature Range
(0 to 60°C [+32 to +140°F])
±0.8%
Output Impedance
<1
Ω
Open and Short-Circuit Protection
Yes
Short-Circuit Current
35 mA typical, 42 mA max.
Output Overvoltage Protection
Yes
Output Response at System Power Up and
Power Down
Power up: +1.2V dc spike for less than 0.4 ms
Power down: 1.2V dc spike for less than 21
ms
Rated Working Voltage
(3)
30V ac/30V dc
Output Group to Bus Isolation
500V ac or 710V dc for 1 minute (qualification
test)
30V ac/30V dc working voltage (IEC Class 2
reinforced insulation)
Module OK LED
On: module has power, has passed internal
diagnostics, and is communicating over the
bus.
Off: Any of the above is not true.
Channel Diagnostics
Over- or under-range by bit reporting
(1)
Output ripple is the amount a fixed output varies with time, assuming a constant load and
temperature.
(2)
Repeatability is the ability of the output module to reproduce output readings when the same
controller value is applied to it consecutively, under the same conditions and in the same direction.
(3)
Rated working voltage is the maximum continuous voltage that can be applied at the output terminal,
including the output signal and the value that floats above ground potential (for example, 10V dc
output signal and 20V dc potential above ground).