Din rail mounting, Replacing a single module within a system – Rockwell Automation 1769-OF4VI CompactLogix Module User Manual
Page 11
![background image](/manuals/579722/11/background.png)
Compact 1769-OF4VI Isolated Analog Output Module 11
Rockwell Automation Publication 1769-IN076B-EN-P - August 2010
6.
Attach the modules to the panel using the mounting screws.
7.
Repeat steps
1
…
6
for any remaining modules.
DIN Rail Mounting
The module can be mounted using the following DIN rails.
•
35 x 7.5 mm (1.38 x 0.30 in.; EN 50 022 - 35 x 7.5)
•
35 x 15 mm (1.38 x 0.59 in.; EN 50 022 - 35 x 15)
Before mounting the module on a DIN rail, close the DIN rail latches. Press
the DIN rail mounting area of the module against the DIN rail. The latches
will momentarily open and lock into place.
Replacing a Single Module Within a System
The module can be replaced while the system is mounted to a panel (or DIN
rail). Follow the steps below in order:
1.
Remove power.
2.
On the module to be removed, remove the upper and lower mounting
screws from the module (or open the DIN latches by using a
screwdriver).
3.
Move the bus lever to the right to disconnect (unlock) the bus.
4.
On the right-side adjacent module, move its bus lever to the right
(unlock) to disconnect it from the module to be removed.
TIP
If mounting more modules, mount only the last one of this group
and put the others aside. This reduces remounting time during
drilling and tapping of the next group.