Compact 1769-OF4VI Isolated Analog Output Module 17

Rockwell Automation Publication 1769-IN076B-EN-P - August 2010

Wire Size and Terminal Screw Torque

Each terminal accepts up to two wires with the following restrictions:

I/O Memory Mapping

Output Data File

For each module, slot x, words 0…3 in the output data file contain the channel
0 …channel 3 output data. Word 4 is used to unlatch any alarm condition that
has been latched. Refer to your module user manual for additional details.

SGN = Sign bit in two’s complement format.

UU = Unlatch under-range (or low-clamp exceeded) alarm.

UO = Unlatch over-range (or high-clamp exceeded) alarm.

Wire Type

Wire Size

Terminal Screw

Torque

Retaining Screw

Torque

Solid

Cu-90 °C (194°F)

#14…#22 AWG

0.68 N•m

(6 in•lbs)

0.46 N•m

(4.1 in-•bs)

Stranded Cu-90 °C (194°F)

#16…#22 AWG

0.68 N•m

(6 in•lbs)

0.46 N•m

(4.1 in•lbs)

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

SGN

Analog Output Data Channel 0

1

SGN

Analog Output Data Channel 1

2

SGN

Analog Output Data Channel 2

3

SGN

Analog Output Data Channel 3

4

UU3 UO3 UU2 UO2 UU1 UO1 UU0 UO0