Installing your plc-5 backup system chapter 3, Inserting the 1785-bcm module into the i/o chassis – Rockwell Automation 1785-BCM_BEM, D17856.5.4 PLC-5 Backup Communication Module User Manual User Manual
Page 32

Installing Your PLC-5 Backup System
Chapter 3
3-9
Table 3.F
Configuring 1785-BCM Series B Channels 1A and 1B using SW2
Configure Channel 1A switches
1
Configure Channel 1B switches
2
for:
1
4
2
5
3
6
Data Highway Plus network at 57.6 kbaud (refer to Chapter 5, section
“Secondary Processor Remote Programming”)
ON
ON
ON
Remote I/O – adapter mode using 57.6 kbaud
ON
ON
OFF
Remote I/O – adapter mode using 115.2 kbaud
ON
OFF
ON
Remote I/O – adapter mode using 230.4 kbaud
ON
OFF
OFF
Relay switching or unused Channel
3
OFF
ON
ON
Remote I/O – scanner mode with 57.6 kbaud
OFF
ON
OFF
Remote I/O – scanner mode with 115.2 kbaud
OFF
OFF
ON
Remote I/O – scanner mode with 230.4 kbaud
OFF
OFF
OFF
1
Switches 1, 2, and 3 determine configuration for Channel 1A.
2
Switches 4, 5, and 6 determine configuration for Channel 1B.
3
Does not function as a smart switch but as a relay with contacts either opened or closed. Also, set
the switches in this configuration if you are not going to use this channel.
Important: The positions of the switches are read at the module power-up.
If the position of the switches is changed after module power-up, the
1785-BCM module does not recognize the new position.
Inserting the 1785-BCM Module into the I/O Chassis
To insert the 1785-BCM module in your I/O chassis, perform the following
steps. We recommend that you insert your 1785-BCM module into the
left-most slot of the first I/O module group in the I/O chassis.
ATTENTION: Remove power from the 1771 I/O chassis
backplane and wiring arm before removing or installing an I/O
module.
Failure to remove power from the backplane or wiring arm
could cause module damage, degradation of performance, or
injury.
Failure to remove power from the backplane could cause injury
or equipment damage due to possible unexpected operation.