Invalid output range selected, Invalid output format selected, Invalid fault value selected – Rockwell Automation 1769-IF4FXOF2F Compact Combination Fast Analog I/O Module User Manual
Page 66: Invalid program/idle value selected
66
Publication 1769-UM019A-EN-P - October 2008
Chapter 4 Module Diagnostics and Troubleshooting
Invalid Output Range Selected
These error codes occur when the 4-bit output range code for the
indicated channel is not one of the assigned output range codes for
the module.
Bit Definitions for Output Range and Output Data Configuration
for details on the assigned output range codes for
the module.
Invalid Output Format Selected
These error codes occur when the 3-bit output format code for the
indicated channel is not one of the assigned output format codes for
the module.
Bit Definitions for Output Range and Output Data Configuration
for details on the assigned output range codes for
the module.
Invalid Fault Value Selected
(1)
These error codes occur when the value entered is not within the
full-range limits of the indicated channel, as determined by the
channel’s output range/type and format setting, or the value entered is
not within the limits set by the indicated channel’s output clamp
values.
Invalid Program/Idle Value Selected
These error codes occur when the value entered is not within the
full-range limits of the indicated channel, as determined by the
channel’s output range/type and format setting, or the value entered is
not within the limits set by the indicated channel’s output clamp
values.
(1) Some controllers do not support alternate output states. Refer to your controller user manual to determine
whether alternate output statues and these associated functions are supported.