Invalid input range selected – Rockwell Automation 1769-IF4FXOF2F Compact Combination Fast Analog I/O Module User Manual
Page 64
![background image](/manuals/579669/64/background.png)
64
Publication 1769-UM019A-EN-P - October 2008
Chapter 4 Module Diagnostics and Troubleshooting
Invalid Input Range Selected
These error codes occur when the 4-bit input range code for the
indicated channel is not one of the assigned input range codes for the
module.
Bit Definitions for Input Range and Input Data Configuration
for details on the assigned input range codes for
each module.
X40D
010
0 0000 1101
Invalid alarm data (channel 0)
X40E
010
0 0000 1110
Invalid alarm data (channel 1)
X40F
010
0 0000 1111
Invalid alarm data (channel 2)
X410
010
0 0001 0000
Invalid alarm data (channel 3)
X411
010
0 0001 0001
Invalid input filter selected (channel 0)
X412
010
0 0001 0010
Invalid input filter selected (channel 1)
X413
010
0 0001 0011
Invalid input filter selected (channel 2)
X414
010
0 0001 0100
Invalid input filter selected (channel 3)
X415
010
0 0001 0101
Invalid output range selected (channel 0)
X416
010
0 0001 0110
Invalid output range selected (channel 1)
X417
010
0 0001 0111
Invalid output format selected (channel 0)
X418
010
0 0001 1000
Invalid output format selected (channel 1)
X419
010
0 0001 1001
Invalid output fault value selected (channel 0)
(2)
X41A
010
0 0001 1010
Invalid output fault value selected (channel 1)
X41B
010
0 0001 1011
Invalid output program/idle value selected (channel 0)
X41C
010
0 0001 1100
Invalid output program/idle value selected (channel 1)
X41D
010
0 0001 1101
Invalid output clamp value selected (channel 0)
X41E
010
0 0001 1110
Invalid output clamp value selected (channel 1)
X41F
010
0 0001 1111
Invalid ramp rate selected (channel 0)
X420
010
0 0010 0000
Invalid ramp rate selected (channel 1)
X421
010
0 0010 0001
Invalid real time sample value
(1) X represents the Don’t Care digit. Module configuration error codes are typically presented in their Hex Equivalent by the programming software.
(2) Some controllers do not support alternate output states. Refer to your controller user manual to determine whether alternate output states and these associated functions
are supported.
Extended Error Codes for Configuration Errors
Hex Equivalent
(1)
Module
Error Code
Extended Error
Information Code
Error Description
Binary
Binary