1779ĆKP5 Troubleshooting Tools
Chapter 6
6Ć5
Diagnostic status bytes contain information about the module, Data
Highway II, and Data Highway Plus.
To read the status bytes, you send a Diagnostic Status command from a
computer on your Data Highway II or Data Highway Plus network. For
information on how to read diagnostic status bytes, refer to the Data
Highway/Data Highway Plus Protocol and Command Set Reference
Manual (Publication 1770-6.5.16).
Diagnostic Status Bytes for Data Highway II
Data Highway II diagnostic status bytes can be read from an intelligent
device (computer) connected to your Data Highway II network. The
following table contains a list of the 1779-KP5’s diagnostic status bytes
for Data Highway II:
Byte
Number
Description
1
00 = Not Used
2
Interface/Processor Type
EE = See Expansion Bytes (Bytes 3 and 4)
3
Interface Type Expansion Byte
1A = 1779ĆKP5
4
Processor Type Expansion
Byte
16 = Data Highway II Information
5
00 = Not Used
6
Data Highway Plus Link
Number
01 = Link 1
02 = Link 2
Etc.
7
Data Highway II Link Number
01 = Link 1
02 = Link 2
Etc.
8
00 = Not Used
9, 10
00 = Not Used
11
Series and Revision
Bits 0Ć4
0 = Revision A
1 = Revision B
Etc.
Bits 5Ć7
0 = Series A
1 = Series B
Etc.
12
Option Switches
Bits 0Ć3: SWĆ5 Data Highway Plus Baud Rate
02 = 230 Kb
04 = 115 Kb
06 = 57.6 Kb
Bits 4Ć7: SWĆ4 Route Updates
00 = Route Updates Disabled
03 = Route Updates Enabled
1779ĆKP5 Diagnostic Status