Installing the 1779ĆKP5 Module

Chapter 3

3Ć7

Switch Assembly SĆ2: Link Address

You use Switch Assembly S-2 to set a unique link address (between 1 and
15) for both the Data Highway II and Data Highway Plus links connected
to the 1779-KP5 in a bridge configuration. The 1779-KP5 uses these link
addresses to route messages. Refer to the following table:

If You Are Using:

Then:

A 1779ĆKP5 in a Bridge Configuration to

Connect Two Data Highway II Links

You need to assign link addresses (using DIP

switches).

A 1779ĆKP5 as a Data Highway II/Data

Highway Plus Interface Using Local

Addressing

You do not assign link addresses.

A 1779ĆKP5 as a Data Highway II/Data

Highway Plus Interface Using Remote

Addressing

You need to assign link addresses (using

stationĆmanagement commands).

Refer to Chapters 4 and 5 for more information on addressing.

OPEN

1

2

3

4

5

6

7

8

16498

Switch Value

(When ON)

1

2

4

8

1

2

4

8

Data Highway Plus
(Switch 1 is the
least significant bit.)

Data Highway II
(Switch 5 is the
least significant bit.)

Important: Do not set the link number to zero unless you only have one
Data Highway II link on the network. The 1779-KP5 uses link zero to
signify the local link message.