D - data organization, Understand the data organization of the module, Appendix d – Rockwell Automation 1747-SDN SLC 500 DeviceNet Scanner Module User Manual User Manual
Page 133: Data organization, Appendix, Input and output image tables
133
Publication 1747-UM655B-EN-P - June 2007
Appendix
D
Data Organization
Understand the Data
Organization of the Module
The module has four data areas to transfer data, status, and command
information between the module and the processor.
•
SLC input image table
•
SLC output image table
•
SLC M1 file
•
SLC M0 file
Input and Output Image Tables
The following table describes the mapping of the 1747-SDN input and
output image tables and the M1 and M0 files.
Words
SLC Input Image
Words
SLC Output Image
0
Status
0
Command
1…31
DeviceNet Input Data (31 words)
1…31
DeviceNet Output Data (31 words)
Words
SLC M1 File
Words
SLC M0 File
0…149
DeviceNet Input Data (150 words)
0…149
DeviceNet Output Data
(150 words)
150…205
Reserved (56 words)
150…223
Reserved
(74 words)
206…209
Device Active Table (4 words)
210
Node Address/Status Indicator (1 word)
211
Scan Counter (1 word)
212…215
Device Idle Table (4 words)
216…219
Device Failure Table (4 words)
220…223
Auto Verify Failure Table
(4 words)
224…255
Explicit Message Program Control (32 words)
224…255
Explicit Message Program Control (32 words)
256…394
Pass-through (139 words)
256…394
Pass-through (139 words)