Publication 1746-UM614B-EN-P - September 2007

Module Specifications 81

Overall Accuracy

We define overall accuracy to include variances in cold-junction
compensation, calibration, non-linearity, and resolution.

Temperature scale
(selectable)

°C or °F and 0.1 °C or 0.1 °F

Millivolt scale, dc
(selectable)

0.1 mV or 0.01 mV

Open-circuit detection
leakage current

20 nA typical

Open-circuit detection
(selectable)

Upscale, downscale, or zero

Time to detect open-circuit

5 s, typical

Input step response

0…99.9% in 600 ms (worst case)

Input resolution

See Input Resolution Graphs on following pages. They show
the smallest measurable value based on combined
hardware and software tolerances.

Display resolution

See Channel Data Word Resolution table on page 51.

Overall module accuracy @
25 °C (77 °F)

See Module Accuracy Table below.

Overall module accuracy
(0… 60 °C, 32…140 °F)

See Module Accuracy Table below.

Overall module drift

See Module Accuracy Table below.

Module update time

Less than 500 ms

Channel turn-off time

Up to one module update time

Input Type

Max Error

(1)

@ 25 °C

Max Error

(1)

@ 77 °F

Temperature Drift

(1)

(0… 60 °C)

J

±1.60 °C

±2.88 °F

±0.042 °C/°C, °F/°F

K

±3.80 °C

±6.84 °F

±0.096 °C/°C, °F/°F

T

±2.05 °C

±3.69 °F

±0.025 °C/°C, °F/°F

E

±2.40 °C

±4.32 °F

±0.058 °C/°C, °F/°F

S

±2.38 °C

±4.29 °F

±0.131 °C/°C, °F/°F

R

±2.23 °C

±4.02 °F

±0.130 °C/°C, °F/°F

B

±3.83 °C

±6.90 °F

±0.109 °C/°C, °F/°F

Attribute

Value