Publication 1746-UM614B-EN-P - September 2007

Application Programming Examples 77

0

]/[

I:2.0

OSR

B3

4

MOV

MOVE
Source

N10:4

Dest

O:1.0

1

I:2.0

] [

0

] [

I:2.0

OSR

B3

5

MOV

MOVE
Source

N10:9

Dest

O:1.0

1

I:2.0

]/[

MEQ

MASKED EQUAL
Source

I:1.4

Mask

FEFF

Compare

N10:4

( )

O:7.0

0

MEQ

MASKED EQUAL
Source

I:1.4

Mask

FEFF

Compare

N10:9

( )

O:7.0

1

Rung 2.4
If the ambient/cabinet selector switch is switched to ambient, and the degrees selector switch
is switched to Celsius, configure channel 0 to read the ambient temperature thermocouple in
degrees Celsius.

Degrees Selector
Switch =
Fahrenheit

Configure Channels

Rung 2.5
If the ambient/cabinet selector switch is switched to cabinet, and the degrees selector switch
is switched to Celsius, configure channel 0 to read the CJC sensor in degrees Celsius.

Degrees Selector
Switch =
Fahrenheit

Rung 2.6
If channel 0 is configured to read the ambient thermocouple, energize the ambient pilot light on
the panel.

Rung 2.7
If channel 0 is configured to read the CJC sensor, energize the cabinet pilot light on the panel.

Configure Channels

Ambient Light

Cabinet Light

Ambient/Cabinet
Selector Switch =
Ambient

Ambient/Cabinet
Selector Switch =
Cabinet