Table 6 - Effective Resolution versus Input Filter Selection for Millivolt Inputs

The table below identifies the number of significant bits used to represent the
input data for each available filter frequency. The number of significant bits is
defined as the number of bits that will have little of no jitter due to noise, and is
used in defining the effective resolution.

Determining Module
Update Time

The module update time is defined as the time required for the module to sample
and convert the input signals of all enabled input channels and provide the
resulting data values to the processor. Module update time can be calculated by
adding the sum of all enabled channel’s times. The module sequentially samples
the enabled channels in a continuous loop as shown below.

Channel update time is dependent upon the input filter selection. This table
shows the channel update times.

Filter Frequency

±50 mV

±100 mV

10 Hz

6 µV

6 µV

50 Hz

9 µV

12 µV

60 Hz

9 µV

12 µV

250 Hz

125 µV

150 µV

500 Hz

250 µV

300 µV

1 kHz

1000 µV

1300 µV

TIP

The resolutions provided by the filters apply to the raw/proportional data
format only.

Channel 4 Disabled

Channel 5 Disabled

No Thermocouple

Calibration Not Active

Sample

Channel 0

Sample

Channel 1

Sample

Channel 2

Sample

Channel 3

Enabled

Enabled

Enabled

Enabled

Sample

Channel 4

Sample

Channel 5

Enabled

Enabled

TC Enabled

Sample

CJC

Calibration

Active

Perform

Calibration

Table 7 - Channel Update Time

Filter Frequency

Channel Update Time

10 Hz

303 ms

50 Hz

63 ms

60 Hz

53 ms

250 Hz

15 ms

500 Hz

9 ms

1 kHz

7 ms