1769-it6 configuration file – Rockwell Automation 1769-IT6 Compact I/O 1769-IT6 Thermocouple/mV Input Module User Manual
Page 140
140
Rockwell Automation Publication 1769-UM004B-EN-P - March 2010
Appendix E Module Configuration by Using a MicroLogix 1500 System and RSLogix 500 Software
For example, to obtain the general status of channel 2 of the module located in
slot e, use address I:e.6/2.
Figure 56 - General Status of Channel 2
1769-IT6 Configuration File
The configuration file contains information you use to define the way a specific
channel functions. The configuration file is explained in more detail in
Configuring Channels on page 40
.
The configuration file is modified by using the programming software
configuration screen. For an example of module configuration by using RSLogix
500 software, see
Configuring the 1769-IT6 Module in a MicroLogix 1500
TIP
The end cap does not use a slot address.
Table 16 - Software Configuration Ch
annel De
faults
(1)
(1)
May be overridden by the software.
Parameter
Default Setting
Disable/Enable Channel
Disable
Filter Frequency
60 Hz
Input Type
Thermocouple Type J
Data Format
Raw/Proportional
Temperature Units
°C
Open-circuit Response
Upscale
Disable Cyclic Calibration
Enable
I:e.6/2
Input File Type
Slot
Word
Bit
Bit Delimiter
Word Delimiter
Element Delimiter
0
1
2
3
Ada
pter
Compact I/O
Compact I/O
Compact I/
O
En
d Cap
Slot Number