Enabling or disabling a channel (bit 15), Selecting data formats (bits 14…12) – Rockwell Automation 1769-IT6 Compact I/O 1769-IT6 Thermocouple/mV Input Module User Manual
Page 43
![background image](/manuals/579251/43/background.png)
Rockwell Automation Publication 1769-UM004B-EN-P - March 2010
43
Module Data, Status, and Channel Configuration Chapter 4
Enabling or Disabling a Channel (bit 15)
You can enable or disable each of the six channels individually by using bit 15.
The module scans enabled channels only. Enabling a channel forces it to be
recalibrated before it measures input data. Disabling a channel sets the channel
data word to zero.
Selecting Data Formats (bits 14…12)
This selection configures channels 0…5 to present analog data in any of these
formats:
•
Raw/Proportional Data
•
Engineering Units x 1
•
Engineering Units x 10
•
Scaled-for-PID
•
Percent Range
TIP
When a channel is not enabled (0), no input is provided to the controller
by the A/D converter. This speeds up the response of the active channels,
improving performance.
Table 2 - Channel Data Word Format
Input
Type
Data Format
Engineering Units x 1
Engineering Units x 10
Scaled-for-PID
Raw/
Proportional Data
Percent
Range
°C
°F
°C
°F
J
-2100…12,000
-3460…21,920
-210…1200
-346…2192
0…16,383
-32,767…32,767
0…10,000
K
-2700…13,700
-4540…24,980
-270…1370
-454…2498
T
-2700…4000
-4540…7520
-270…400
-454…752
E
-2700…10,000
-4540…18,320
-270…1000
-454…1832
R
0…17,680
320…32,140
0…1768
32…3214
S
0…17,680
320…32,140
0…1768
32…3214
B
3000…18,200
5720…32,767
(1)
300…1820
572…3308
N
-2100…13,000
-3460…23,720
-210…1300 -346…2372
C
0…23,150
320…32,767
(1)
0…2315
32…4199
±50 mV
-5000…5000
-500…500
(2)
±100 mV
-10,000…10,000
-1000…1000
(1) Type B and C thermocouples cannot be represented in engineering units x1 (°F) above 3276.7 °F; therefore, it will be treated as an over-range error.
(2) When millivolts are selected, the temperature setting is ignored. Analog input date is the same for °C or °F selection.