Enabling or Disabling a Channel (bit 15)

You can enable or disable each of the six channels individually by using bit 15.
The module scans enabled channels only. Enabling a channel forces it to be
recalibrated before it measures input data. Disabling a channel sets the channel
data word to zero.

Selecting Data Formats (bits 14…12)

This selection configures channels 0…5 to present analog data in any of these
formats:

Raw/Proportional Data

Engineering Units x 1

Engineering Units x 10

Scaled-for-PID

Percent Range

TIP

When a channel is not enabled (0), no input is provided to the controller
by the A/D converter. This speeds up the response of the active channels,
improving performance.

Table 2 - Channel Data Word Format

Input
Type

Data Format

Engineering Units x 1

Engineering Units x 10

Scaled-for-PID

Raw/
Proportional Data

Percent
Range

°C

°F

°C

°F

J

-2100…12,000

-3460…21,920

-210…1200

-346…2192

0…16,383

-32,767…32,767

0…10,000

K

-2700…13,700

-4540…24,980

-270…1370

-454…2498

T

-2700…4000

-4540…7520

-270…400

-454…752

E

-2700…10,000

-4540…18,320

-270…1000

-454…1832

R

0…17,680

320…32,140

0…1768

32…3214

S

0…17,680

320…32,140

0…1768

32…3214

B

3000…18,200

5720…32,767

(1)

300…1820

572…3308

N

-2100…13,000

-3460…23,720

-210…1300 -346…2372

C

0…23,150

320…32,767

(1)

0…2315

32…4199

±50 mV

-5000…5000

(2)

-500…500

(2)

±100 mV

-10,000…10,000

(2)

-1000…1000

(2)

(1) Type B and C thermocouples cannot be represented in engineering units x1 (°F) above 3276.7 °F; therefore, it will be treated as an over-range error.

(2) When millivolts are selected, the temperature setting is ignored. Analog input date is the same for °C or °F selection.