Rockwell Automation 1756-EN3TR ControlLogix EtherNet/IP Communication Module Installation Instructions User Manual
Page 23

23
Publication
1756-IN612B-EN-P - December 2009
Immunity, radiated RF
•
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80%AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at
900 MHz
10V/m with 200 Hz 50% Pulse 100%AM at
1890 MHz
3V/m with 1 kHz sine-wave 80%AM from
2000…2700 MHz
Immunity, EFT/B
•
IEC 61000-4-4
±3 kV at 5 kHz on Ethernet port
Immunity, surge transient
•
IEC 61000-4-5
±2 kV line-earth(CM) on Ethernet port
Immunity, conducted RF
•
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80%AM
from 150 kHz…80 MHz
Certifications - 1756-EN2TR and 1756-EN3TR
Certification
Value
When product is marked. See the Product Certification link a
for Declarations of Conformity,
Certificates, and other certification details
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.
FM
FM Approved Equipment for use in Class I Division 2 Group A,B,C,D
Hazardous Locations
Environmental Specifications - 1756-EN2TR and 1756-EN3TR
Attribute