Specifications, Specifications 21 – Rockwell Automation 1756-EN3TR ControlLogix EtherNet/IP Communication Module Installation Instructions User Manual
Page 21

21
Publication
1756-IN612B-EN-P - December 2009
Specifications
Technical Specifications - 1756-EN2TR and 1756-EN3TR
Attribute
Value
Module location
Any slot in the ControlLogix chassis
Backplane current (mA)
at 5.1V DC
1 A
Backplane current (mA)
at 24V DC
3 mA
Isolation voltage
30 V (continuous), Basic Insulation Type, Ethernet to system
No isolation between USB and system
Type tested at 853V AC for 60 s
Power consumption,
max
5.1 W
Power dissipation
5.1 W
Wire size
Ethernet connections:
RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e
minimum cable according to TIA 568-B.1 or Category 5 cable
according to ISO/IEC 24702.
Wiring category
1 - on communication ports
(1)
(1)
Use this Conductor Category information for planning conductor routing.
Refer to Industrial Automation Wiring and Grounding Guidelines, publication
.
North American temp
code
T4A
Recommended USB
cable for USB port
For hazardous environments, Samtec cable, PN RSP-119350
USB port
USB 1.1
USB device,
USB series B receptacle
Enclosure type rating
None (open-style)