Environmental Specifications - 1756-EN2TR and 1756-EN3TR
Attribute
Value
Temperature, operating
•
IEC 60068-2-1 (Test Ad, Operating
Cold)
•
IEC 60068-2-2 (Test Bd, Operating
Dry Heat)
•
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
0…60 °C (32…140 °F)
Temperature, nonoperating
•
IEC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold)
•
IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat)
•
IEC 60068-2-14 (Test Na,
Unpackaged Nonoperating Thermal
Shock)
-40…85 °C (-40…185 °F)
Relative humidity
•
IEC 60068-2-30 (Test Db,
Unpackaged Damp Heat)
5…95% noncondensing
Vibration
•
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
•
EC 60068-2-27 (Test Ea, Unpackaged
Shock)
30 g
Shock, nonoperating
•
IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
50 g
Emissions
•
CISPR 11
Group 1, Class A
Immunity, ESD
•
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges