Invalid output range selected, Invalid output format selected – Rockwell Automation 1769-OF4 Compact Analog Output Module User Manual
Page 48
48
Publication 1769-UM020A-EN-P - December 2009
Chapter 4 Module Diagnostics and Troubleshooting
Invalid Output Range Selected
These error codes occur when the 4-bit output range code for the
indicated channel is not one of the assigned output range codes for
the module.
See
Bit Definitions for Type/Range and Data Format Configuration
for details on the assigned output range codes for
the module.
Invalid Output Format Selected
These error codes occur when the 3-bit output format code for the
indicated channel is not one of the assigned output format codes for
the module.
See
Bit Definitions for Type/Range and Data Format Configuration
for details on the assigned output range codes for
the module.
X40D
010
0 0000 1101
Invalid program/idle value (channel 0)
X40E
010
0 0000 1110
Invalid program/idle value (channel 1)
X40F
010
0 0000 1111
Invalid program/idle value (channel 2)
X410
010
0 0001 0000
Invalid program/idle value (channel 3)
X411
010
0 0001 0001
Invalid clamp value (channel 0)
X412
010
0 0001 0010
Invalid clamp value (channel 1)
X413
010
0 0001 0011
Invalid clamp value (channel 2)
X414
010
0 0001 0100
Invalid clamp value (channel 3)
X415
010
0 0001 0101
Invalid ramp rate (channel 0)
X416
010
0 0001 0110
Invalid ramp rate (channel 1)
X417
010
0 0001 0111
Invalid ramp rate (channel 2)
X418
010
0 0001 1000
Invalid ramp rate (channel 3)
(1) X represents the Don’t Care digit. Module configuration error codes are typically presented in their Hex Equivalent by the programming software.
Extended Error Codes for Configuration Errors
Hex Equivalent
(1)
Module
Error Code
Extended Error
Information Code
Error Description
Binary
Binary