Error codes – Rockwell Automation 1769-OF4 Compact Analog Output Module User Manual
Page 47
![background image](/manuals/579206/47/background.png)
Publication 1769-UM020A-EN-P - December 2009
47
Module Diagnostics and Troubleshooting Chapter 4
Error Codes
Error codes can help troubleshoot your module.
During system configuration, if you set the fields in the configuration
file to invalid or unsupported values, the module generates a
configuration error and the system controller enters a Fault condition.
The invalid configuration data must be corrected and the program
downloaded again for the system to enter Run mode. You cannot
change module configuration data while the system is in Run mode.
Any changes are ignored by the module, which continues to operate
with its previous configuration.
Extended Error Codes for Hardware Errors
Error Type
Hex
Equivalent
(1)
Module
Error
Code
Extended Error
Information
Code
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No error
General Common
Hardware Error
X200
001
0 0000 0000
General hardware error; no additional information
X201
001
0 0000 0001
Power-up reset state
Hardware-
specific Error
X300
001
1 0000 0000
General hardware error
X301
001
1 0000 0001
Microprocessor hardware error
X302
001
1 0000 0010
D/A converter communication error
(1) X represents the Don’t Care digit. Module hardware error codes are typically presented in their Hex Equivalent by the programming software.
Extended Error Codes for Configuration Errors
Hex Equivalent
(1)
Module
Error Code
Extended Error
Information Code
Error Description
Binary
Binary
X400
010
0 0000 0000
General configuration error; reserve bits set to 1
X401
010
0 0000 0001
Invalid output range selected (channel 0)
X402
010
0 0000 0010
Invalid output range selected (channel 1)
X403
010
0 0000 0011
Invalid output range selected (channel 2)
X404
010
0 0000 0100
Invalid output range selected (channel 3)
X405
010
0 0000 0101
Invalid output format selected (channel 0)
X406
010
0 0000 0110
Invalid output format selected (channel 1)
X407
010
0 0000 0111
Invalid output format selected (channel 2)
X408
010
0 0000 1000
Invalid output format selected (channel 3)
X409
010
0 0000 1001
Invalid fault value (channel 0)
X40A
010
0 0000 1010
Invalid fault value (channel 1)
X40B
010
0 0000 1011
Invalid fault value (channel 2)
X40C
010
0 0000 1100
Invalid fault value (channel 3)