Chapter 8, 8 - troubleshooting the module, Troubleshooting with led indicators – Rockwell Automation 1746-BTM Barrel Temperature Control Module User Manual User Manual
Page 65: Troubleshooting with led indicators -1, Troubleshooting the module, Chapter

1
Publication 1746-UM010B-EN-P - April 2001
Chapter
8
Troubleshooting the Module
This chapter provides troubleshooting guidelines.
Troubleshooting with LED
Indicators
The front panel of the module contains five green LED indicators for
channel status and one green LED indicator for module status.
We present a table of indications, probable causes, and recommended
action. See Table 8.A on page 8-3 and Table 8.B on page 8-4 for a
listing of error codes.
INPUT
ISOLATED
CHANNEL
STATUS
MODULE STATUS
0
2
1
3
LED: When: Indicates
Channel
Status
On channel is correctly configured
when you enable the channel
Flashing channel fault condition
Module
Status
Flashing communication occurring between
SLC processor and BTM module
On self-check completed OK
Indication
Probable Cause
Recommended Action:
all indicators
are OFF
no power to module
check power to I/O chassis
recycle power as necessary
module performing self–check
wait until self check is complete
module performing calibration
wait until calibration is complete
possible short on the module
LED failure
replace module
channel status
indicator is ON
channel is correctly configured
when you enable the channel
normal operation
during calibration, the channel is
properly configured for the high–end of
millivolt range
normal calibration
channel status
indicator is flashing
fault condition, such as open circuit or
an under/over range condition
correct fault condition
during calibration, the channel is
properly configured for the low–end of
millivolt range
normal calibration