Global commands to all loops, Global commands to all loops -9 – Rockwell Automation 1746-BTM Barrel Temperature Control Module User Manual User Manual
Page 55

Publication 1746-UM010B-EN-P - April 2001
Control and Autotune a Loop 5-9
Global Commands to All Loops
Remember that the module returns the control variable (CV) of each
loop to the input image table as both a numeric value (current CV)
and a time–proportioned output (TPO). For additional information,
Refer to BTM201.rss M1, M0, Input Image, Output Image, and Rotator
Code Data Table on page 9-4 and BTM50220.RSS M1, M0, Input
Image, Output Image, and Rotator Code Data Table on page 9-8.
Word
Bit
To Control
Selected By
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
12
0
Temperature units
F =0;C =1
1
Autotune invoke
invoke =1;None = 0
2
Autotune abort
Abort = 1;None =0
3
Reset error codes
None =0; Reset =1
3-7
Reserved
8-10
Selection of Reported value
if bit 11 is not set in the
output image buffer
N10:192/11
Current Setpoint
0
0
1
Current Error Value
0
1
0
Current CV (loop output)
0
1
1
Current Error Code
1
0
0
Cold Junction Temperature
1
0
1
Firmware Revision Number
1
1
0
Selection of Reported value
if bit 11 is set in the output
image buffer
N10:192/11
P Contribution
0
0
1
I Contribution
0
1
0
D Contribution
0
1
1
Pre-set Point
1
0
0
Wait Period
1
0
1
Reserved
1
1
0
11
Advanced Rotator Values
Disable = 0;Enable =1
12
MO download request
None =0; Download =1
13
M1 download request
None =0; Download =1
14
M0 upload request
None =0; Upload =1
15
M1 upload request
None =0; Upload =1
13
0-15
Reserved
14
0-15
Calibration word
15
0-15
Reserved
IMPORTANT
The sample program returns all six variables. For
their data table locations, Refer to BTM201.rss Data
Table Layout on page 9-2 and BTM50220.RSS Data
table layout on page 9-7.