Rockwell Automation 1734-485ASC POINT I/O ASCII User Manual User Manual
Page 59

Publication 1734-UM009B-EN-P - July 2003
Specifications A-3
Specifications - 1734-232ASC, -485ASC Modules (Continued)
EFT/B Immunity
IEC 61000-4-4:
+4kV at 2.5kHz on power ports
+2kV at 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5:
+1kV line-line(DM) and +2kV line-earth(CM) on
signal ports
+1kV line-line(DM) and +2kV line-earth(CM) on
power ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from
150kHz to 80MHz
Emissions
CISPR 11
Group 1, Class A
Enclosure Type Rating
None (open-style)
Conductors
Wire Size
14 AWG (2.5mm
2
) - 22AWG (0.25mm
2
) solid or
stranded copper wire rated at 75
°C or greater
3/64 inch (1.2mm) insulation
Category
2
1
RS-232 Field Wiring Terminations
0 - Tx
1 - Rx
2 - NC
3 - NC
4 - NC
5 - NC
6 - NC
7 - SG
RS-485 Field Wiring Terminations
0 - S+
1 - NC
2 - S-
3 - NC
4 - NC
5 - NC
6 - CG
7 - SG
RS-422 Field Wiring Terminations
0 - Tx+
1 - Rx+
2 - Tx-
3 - Rx-
4 - NC
5 - NC
6 - CG
7 - SG
Terminal Base Screw Torque
7 pound-inches (0.6Nm) maximum
Mass
1.22 oz/34.6 grams
Agency Certification (when product is
marked)
CE
2
- European Union 89/335/EEC EMC
Directive, compliant with:
EN 50081-2; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
C-Tick
2
- Australian Radiocommunications Act
compliant with AS/NZS 2064, Industrial
Emissions
Installation Instructions
Publication 1734-IN588
1
Use this conductor category information for planning conductor routing as described in publication 1770-4.1,
“Industrial Automation Wiring and Grounding Guidelines.”
2
See the Product Certification link at www.ab.com for Declaration of Conformity, Certificates, and other
certification details.