2, configuring your ascii module, About communications, Configuring your ascii module – Rockwell Automation 1734-485ASC POINT I/O ASCII User Manual User Manual
Page 27: Chapter 2, About communications -1, Chapter
1
Publication 1734-UM009B-EN-P - July 2003
Chapter
2
Configuring Your ASCII Module
About Communications
The ASCII modules have DeviceNet-to-serial link communication that
provides a flexible DeviceNet interface to a wide variety of ASCII
devices. Used with the POINT I/O system, these modules allow you to
easily and conveniently connect and integrate peripheral products
with RS-232, RS-485, or RS-422 serial ports into a DeviceNet system.
Data can be exchanged with the master through a polled, cyclic, or
change-of-state connection. Bit-Strobe Command Response Messaging
and the Unconnected Message Manager (UCMM) are not supported
1
.
The module produces and consumes data as follows:
1
If you are not familiar with these terms, see the DeviceNet Specification for definitions (online: www.odva.org).
Table 2.1 Produce/Consume Data
I/O Connection Type
Consumes
Produces
Polled
A
4-132 bytes
4-132 bytes
Cyclic
A
4-132 bytes
4-132 bytes
Change of State
A
4-132 bytes
4-132 bytes
A
Default values are 24 bytes.
ATTENTION
!
The ASCII modules are not compatible with the
1734-APB PROFIBUS adapter.