Parameter list, Parameter list -10 – Rockwell Automation 1734-485ASC POINT I/O ASCII User Manual User Manual
Page 36

Publication 1734-UM009B-EN-P - July 2003
2-10 Configuring Your ASCII Module
Parameter List
Use this table for information on configuring your ASCII module’s
parameters.
Table 2.3 Parameter List
Parameter
Parameter
Instance
Access
Description
Parameter Choices
Default
Setting
Default
Value
Data Type
Serial Port Parameters
Serial Character
Framing
1
Get/Set
Defines the number
of data bits, stop
bits and parity in
data character
frames
0 = 7N2
1 = 7E1
2 = 7O1
3 = 8N1
4 = 8N2
5 = 8E1
6 = 8O1
7 = 7E2
8 = 7O2
7N2
0
USINT
Serial Port Comm
Speed
2
Get/Set
Defines the baud
rate of the serial
port
0 = 9600
1 = 1200
2 = 2400
3 = 4800
4 = 19.2k
5 = 38.4k
9600 baud
0
USINT
Serial Port Receive from ASCII Device
Max Number of
Receive Chars
3
Get/Set
Maximum number of
characters the
1734-232ASC
module expects to
receive into its
ASCII port from the
serial device
1-128
20 chars
20
USINT
Receive Record
Start Mode
4
Get/Set
Selects whether or
not the start
delimiter is included
with the receive
data
0 = No Start
Delimiter
1 = Exclude Start
Delimiter
2 = Include Start
Delimiter
No Start
Delimiter
0
USINT
Receive Start
Delimiter
5
Get/Set
Character which
identifies the
beginning of the
data string from the
ASCII device when
the length is
specified as 0
Any valid standard
ASCII character
(0-127, 0-255)
Colon
0x3A
USINT
Receive Record End
Mode
6
Get/Set
Selects whether or
not the End
delimiter is included
with the received
data
0 = No End Delimiter
1 = Exclude End
Delimiter
2 = Include End
Delimiter
Include End
Delimiter
2
USINT
Receive End
Delimiter
7
Get/Set
Character which
identifies the end of
the data string from
the ASCII device
when the length is
specified as 0
Any valid standard
ASCII character
(0-127, 0-255)
Carriage
return
D
hex
USINT