beautypg.com

3 specifications – Rockwell Automation 931U-C9C7C-BC Configurator Software User Manual

Page 18

background image

Page | 18

4.3 Specifications

 

Input types

Thermocouple 

Range ‐200...+1820 °C 
Types B, E, J, K , L, N, R, S, T to IEC 60584 plus custom specific 

RTD  

2, 3, 4 wire, within the range ‐200...+850 °C, for Pt100, Pt1000 to 
IEC 60571 and for Ni100 / Ni1000 to DIN 43760, for Cu10 and,100 plus 
custom specific 

Potentiometer  

10 Ω...100 kΩ 

Resistance  

10 Ω...5 kΩ 

Frequency  

2 Hz...100 kHz 

Voltage  

within the range ‐200...600 mV (min span 4 mV),  
within the range ‐20...50 V DC (min span 0.5 V) 

Current  

within the range ‐20...50 mA (min span 1 mA) 

Current Loop supply 

+24 V DC 

Sensor break output 

Selectable between ‐2% and 102% output 

Analog Output

 

DC voltage 

0...5, 1...5, 0...10, 2...10 V or span‐settable between ‐10...10 V  
(min span 2.5 V) 

DC current 

0...20, 4...20, 0...10 mA, or span‐settable between 0...20 mA  
(min span 5 mA) 

Max load (current / voltage) 

700 Ω / >10 kΩ (>20 kΩ for ‐10 V…+10 V) 

Action  

Direct or Inverted Operation 

Digital Output Relay

 

Relays 

2 x SPCO 

Max voltage and current AC 

250 V AC / 2 A 

Max voltage and current DC 

30 V DC / 2 A 

General Data

 

Rated voltage 

24...240 V AC/DC 

24…36 V AC / 24…50 V AC (ATEX Zone 2)