Analog Output status with alarm

• User may select output value under fault condi‐

tions 

• Output compliant with NAMUR recommenda‐

tions (NE43) can be set (< 3.6 mA or > 21 mA) 

 

Input fault detection

Input faults such as short circuit or open circuit can 
be detected for most input types. These are shown 
in the table below. 

 

Input type

Detection

Open cir-

cuit

Short cir-

cuit

Thermocouple 

Yes 

Yes 

RTD 

Yes 

Yes 

Millivolts 

Yes 

No 

Volts (Positive) 

Yes 

No 

Milliamps  
(Passive) 

Yes* 

No 

Milliamps (Ac‐
tive) 

Yes 

Yes 

Resistance 

Yes 

Yes 

Potentiometer 

Yes 

Yes** 

Table 2 

Input fault detection 

*  Open circuit not detected for live zero ranges 

** Short circuit for end‐to‐end