Repeat cycle operation – Rockwell Automation 700-HX Multifunction Digital Timer User Manual
Page 27

Publication 700-UM002B-EN-D - June 2010
3-16 Functions
Repeat Cycle Operation
Output mode TOFF: Flicker OFF start 1 (Timer resets when power comes ON)
Output mode TON: Flicker ON start 1 (Timer resets when power comes ON)
Output mode TOFF-1: Flicker OFF start 2 (Timer does not reset when power comes ON)
Power
Start signal
Gate
Reset
Control output
OFF time
Timing
diagram
UP
ON time
Sustained
Output
DOWN
0
OFF time
ON time
0
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
* Normal output operation will not be possible if the
ON/OFF set time is too short.
Set the value to at least 100 ms (contact output
type).
** Start signal input is disabled during timing.
Basic Operation
Power
**
Start signal
input
Timing
ON
Output
Timing
OFF
Timing
ON
Timing
OFF
Power
Start signal
Gate
Reset
Control output
OFF time
Timing
diagram
UP
ON time
Sustained
Output
DOWN
OFF time
ON time
0
0
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (ON at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
* Normal output operation will not be possible if the
ON/OFF set time is too short.
Set the value to at least 100 ms (contact output
type).
** Start signal input is disabled during timing.
Basic Operation
Power
**
Start signal
input
Timing
OFF
Output
Timing
ON
Timing
OFF
Timing
ON