Z mode – Rockwell Automation 700-HX Multifunction Digital Timer User Manual
Page 25

Publication 700-UM002B-EN-D - June 2010
3-14 Functions
Z Mode
Output quantity can be adjusted by changing the cycle time set in the
adjustment level to 1 and by changing the ON duty (%) set value. The set value
shows the ON duty (%) and can be set to a value between 0 and 100 (%).
When the cycle time is 0, the output will always be OFF. When the cycle time
is not 0 and when ON duty has been set to 0 (%), the output will always be
OFF. When ON duty has been set to 100 (%), the output will always be ON.
Output mode D: Signal OFF-delay (Timer resets when power comes ON.)
Output mode E: One Shot (Timer resets when power comes ON.)
Output Mode F: Cumulative (Timer does not reset when power comes ON)
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
The control output is ON when the start signal is
ON (except when the power is OFF or the reset is
ON).
The timer is reset when the time is up.
* Output functions only during start signal input when
setting is 0.
** Start signal input is enabled during timing.
Basic Operation
Power
**
Start signal
input
Output
Timing
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Timing starts when the start signal comes ON.
The control output is reset when time is up.
While the start signal is ON, the timer starts when
power comes ON or when the reset input goes OFF.
* Output is disabled when the setting is 0.
** Start signal input is enabled during timing.
Basic Operation
Power
**
Start signal
input
Output
Timing
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Start signal enables timing (timing is stopped when the
start signal is OFF or when the power is OFF).
A sustained control output is used.
*Output is instantaneous when setting is 0.
Sustained
Basic Operation
Power
Start signal
input
Output
Timing
Timing