Rockwell Automation 20D PowerFlex 700H to 700S Phase II Control Conversion (Frames 9...14) User Manual
Page 37
37
Publication 20C-IN001D-EN-P
Important: Minimum inside bend radius for fiber-optic cable is 25.4 mm (1
in.). Any bends with a shorter inside radius can permanently
damage the fiber-optic cable. Signal attenuation increases with
decreased inside bend radii.
5. Carefully connect the ribbon cable from P1 on the Main Control circuit
board to J2 on the High Power Fiber Optic Interface circuit board and ribbon
cable P2 on the Main Control circuit board to J1 on the High Power Fiber
Optic Interface circuit board.
6. Make the following connections on the High Power Fiber Optic Interface
circuit board:
– LED cable to J16
– DPI cable to J4
– 24V Auxiliary Power Supply cable to J15
7. Install all other connections on the 700S Phase II Main Control assembly.
Fiber-Optic
Sockets
J17
J2
J1
J16
J4
J15
J5
Frame 10, 11 and 13
High Power Fiber Optic
Interface circuit board
shown.
=