Events – Rockwell Automation 20-COMM-B BACnet MS/TP Adapter User Manual
Page 50

5-8
Troubleshooting
Events
Many events in the Event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:
Code Event Description
1
No Event
Empty event queue entry.
2
DPI Bus Off Flt
A bus-off condition was detected on DPI. This event may be caused by
loose or broken cables or by noise.
3
Ping Time Flt
A ping message was not received on DPI within the specified time.
4
Port ID Flt
The adapter is not connected to a correct port on a DPI product.
5
Port Change Flt
The DPI port changed after start up.
6
Host Sent Reset
The drive sent a reset event message.
7
EEPROM Sum Flt
The EEPROM in the adapter is corrupt.
8
Online @ 125 kbps The adapter detected the drive communicating at 125 kbps.
9
Online @ 500 kbps The adapter detected the drive communicating at 500 kbps.
10
Bad Host Flt
The adapter was connected to an incompatible product.
11
Dup Port Flt
Another peripheral with the same port number is already in use.
12
Type 0 Login
The adapter has logged in for Type 0 control.
13
Type 0 Time Flt
The adapter has not received a Type 0 status message within the
specified time.
14
DL Login
The adapter has logged into a Datalink.
15
DL Reject Flt
The drive rejected an attempt to log in to a Datalink because the Datalink
is not supported or is used by another peripheral.
16
DL Time Flt
The adapter has not received a Datalink message within the specified time.
17
Reserved
—
18
Control Disabled
The adapter has sent a “Soft Control Disable” command to the drive.
19
Control Enabled
The adapter has sent a “Soft Control Enable” command to the drive.
20
Message Timeout
A client-server message sent by the adapter was not completed within 1 sec.
21
Fault Cfg Error
One of the Flt Cfg XX In parameters is set to a value greater than 65535
and the drive requires a 16-bit value.
22
App Updated
New application firmware was detected.
23
Net Comm Flt
The adapter detected a communications fault on the network.
24
Net Sent Reset
The adapter received a fault from the network.
25
Net Close Flt
An I/O connection from the network to the adapter was closed.
26
Net Idle Flt
The adapter is receiving “idle” packets from the network.
27
Net Open
An I/O connection from the network to the adapter has been opened.
28
Net TImeout Flt
An I/O connection from the network to the adapter has timed out.
29
PCCC IO Close
The device sending PCCC Control messages to the adapter has set the
PCCC Control Timeout to zero.
30
PCCC IO Open
The adapter has begun receiving PCCC Control messages.
31
PCCC IO Time Flt
The adapter has not received a PCCC Control message for longer than
the PCCC Control Timeout.
32
Watchdog T/O Flt
The software detects a failure.
33
EEPROM Init
A blank EEPROM map revision was detected.
34
Normal Startup
The adapter successfully started up.
35
Manual Reset
The adapter was reset by changing its Reset Module parameter.