Many events in the event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help you
or Allen-Bradley personnel troubleshoot the problem. The following events
may appear in the event queue:
Table 5.B Adapter Events
Code Event
Description
1
No Event
Empty event queue entry.
2
DPI Bus Off Flt
A bus-off condition was detected on DPI. This event may be caused by loose or broken cables or by noise.
3
Ping Time Flt
A ping message was not received on DPI within the specified time.
4
Port ID Flt
The adapter is not connected to a correct port on a DPI product.
5
Port Change Flt
The DPI port changed after start up.
6
Host Sent Reset
The drive sent a reset event message.
7
EEPROM Sum Flt The EEPROM in the adapter is corrupt.
8
Online @ 125kbps The adapter detected that the drive is communicating at 125 kbps.
9
Online @ 500kbps The adapter detected that the drive is communicating at 500 kbps.
10
Bad Host Flt
The adapter was connected to an incompatible product.
11
Dup Port Flt
Another peripheral with the same port number is already in use.
12
Type 0 Login
The adapter has logged in for Type 0 control.
13
Type 0 Time Flt
The adapter has not received a Type 0 status message within the specified time.
14
DL Login
The adapter has logged into a Datalink.
15
DL Reject Flt
The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another
peripheral.
16
DL Time Flt
The adapter has not received a Datalink message within the specified time.
17
Reserved
Not used.
18
Control Disabled
The adapter has sent a “Soft Control Disable” command to the drive.
19
Control Enabled
The adapter has sent a “Soft Control Enable” command to the drive.
20
Message Timeout
A Client-Server message sent by the adapter was not completed within 1 sec.
21
Flt Cfg Error
One of the Flt Cfg xx parameters is set to a value greater than 65535 and the drive requires a 16-bit value.
22
App Updated
Startup sequence detected new application firmware.
23
EN Comm Flt
The adapter detected a communications fault on the network.
24
EN Sent Reset
The adapter received a reset from the network.
25
EN Close Flt
An I/O connection from the network to the adapter was closed.
26
EN Idle Flt
The adapter is receiving “idle” packets from the network.
27
EN Open
An I/O connection from the network to the adapter has been opened.
28
EN Timeout Flt
An I/O connection from the network to the adapter has timed out.
29
PCCC IO Close
The device sending PCCC Control messages to the adapter has set the PCCC Control Timeout to zero.
30
PCCC IO Open
The adapter has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a
non-zero value).
31
PCCC IO Time Flt The adapter has not received a PCCC Control message for longer than the PCCC Control Timeout.
32
Watchdog T/O Flt
The software detects a failure.
33
EEPROM Init
Startup sequence detected a blank EEPROM map revision.
34
Normal Startup
The adapter successfully started up.
35
Manual Reset
The adapter was reset by changing its Reset Module parameter.
36
EN Link Down
The Ethernet link was removed from the adapter.
37
EN Link Up
An Ethernet link is available for the adapter.
38
BOOTP Response The adapter received a response to its BOOTP request.
39
Dup IP Addr
The adapter uses the same IP address as another device on the network.
40-41 Reserved
Not used.
42
Email Failed
The adapter encountered an error attempting to send a requested e-mail message.
43-48 Reserved
Not used.