Quick start, Quick start -5 – Rockwell Automation 20-COMM-M Modbus/TCP Adapter User Manual
Page 13
Getting Started
1-5
20-COMM-M Modbus/TCP Adapter User Manual
Publication 20COMM-UM014C-EN-P
Quick Start
This section is provided to help experienced users quickly start using the
adapter. If you are unsure how to complete a step, refer to the referenced
chapter.
Step
Action
Refer to…
1
Review the safety precautions for the adapter.
Throughout This Manual
2
Verify that the PowerFlex drive is properly installed.
Drive User Manual
3
Install the adapter.
Verify that the PowerFlex drive is not powered. Then, connect the
adapter to the network using an Ethernet cable and to the drive
using the Internal Interface cable. Use the captive screws to
secure and ground the adapter to the drive.
Note: When installing the adapter in a DPI External Comms Kit,
refer to the 20-XCOMM-DC-BASE Installation Instructions
(publication 20COMM-IN001) supplied with the kit.
PowerFlex 7-Class DPI
Network Communication
Adapter Installation
Instructions (publication
20COMM-IN004) and
,
4
Apply power to the adapter.
A. The adapter receives power from the drive. Verify that the
adapter is installed correctly and then apply power to the drive.
The status indicators should be green. If they flash red, there is
a problem. Refer to
,
.
B. Configure/verify key drive parameters.
,
5
Configure the adapter for your application.
Set adapter parameters for the following functions as required by
your application:
•
IP address, subnet mask, and gateway address
•
Data rate
•
I/O configuration
•
Fault action
,
6
Set up the master device to communicate with the adapter.
Use a network tool to configure the master device on the Modbus/
TCP network.
Instructions for your
network tool