Rockwell Automation 20-COMM-M Modbus/TCP Adapter User Manual
Page 41
Using Modbus/TCP Function Codes
4-5
20-COMM-M Modbus/TCP Adapter User Manual
Publication 20COMM-UM014C-EN-P
Table 4.D Logic Command Registers (to Drive from Controller)
Table 4.E
shows the Logic Command register used for writing 16-bit
commands or multiple decimal values.
Table 4.E Logic Command Register
To set the Reference, you must write the decimal values to register
addresses 10003 and 10004 (
Table 4.F
) using Function Code 16 or 23.
Register
Address
Logic Command
Bit
PowerFlex 70/700 Example
Description
Values
1
0
Stop
0 = Not Stop
1 = Stop
2
1
Start
(1)
(2)
(1)
A “0 = Not Stop” condition (logic 0) must first be present before a “1 = Start” condition will start the drive.
(2)
To perform this command, the value must change from “0” to “1.”
0 = Not Start
1 = Start
3
2
Jog
0 = Not Jog (Par. 100)
1 = Jog
4
3
Clear Faults
(2)
0 = Not Clear Faults
1 = Clear Faults
5
4
Direction
Register Address
6
5
6
5
0
0
= No Command
0
1
= Forward Command
1
0
= Reverse Command
1
1
= Hold Direction Control
7
6
Local Control
0 = No Local Control
1 = Local Control
8
7
MOP Increment
0 = Not Increment
1 = Increment
9
8
Accel Rate
Register Address
10
9
10
09
0
0
= No Command
0
1
= Accel Rate 1 Command (Par. 140)
1
0
= Accel Rate 2 Command (Par. 141)
1
1
= Hold Accel Rate
11
10
Decel Rate
Register Address
12
11
12
11
0
0
= No Command
0
1
= Decel Rate 1 Command (Par. 142)
1
0
= Decel Rate 2 Command (Par. 143)
1
1
= Hold Decel Rate
13
12
Reference Select Register Address
14
13
15
14
13
15
14
0
0
0
= No Command
0
0
1
= Ref A Select (Par. 90)
0
1
0
= Ref B Select (Par. 93)
0
1
1
= Preset 3 (Par. 103)
1
0
0
= Preset 4 (Par. 104)
1
0
1
= Preset 5 (Par. 105)
1
1
0
= Preset 6 (Par. 106)
1
1
1
= Preset 7 (Par. 107)
16
15
MOP Decrement
0 = Not Decrement
1 = Decrement
Register
Address
Description
Values
10001
Logic Command
16-bit word. Bit definitions for PowerFlex 70/700 drives are in
Table 4.D
. For other products, refer to their documentation.