Advanced program group parameters – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual
Page 22

English-22
PowerFlex 400 Adjustable Frequency AC Drive Quick Start
Advanced Program Group Parameters
No.
Parameter
Min/Max
Display/Options
Default
A141 [Purge Frequency]
0.0/320.0 Hz
0.1 Hz
5.0 Hz
A142 [Internal Freq]
0.00/320.00 Hz
0.01 Hz
60.00 Hz
A143
A144
A145
A146
[Preset Freq 0]
[Preset Freq 1]
[Preset Freq 2]
[Preset Freq 3]
0.0/320.0 Hz
0.1 Hz
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
A147 [Accel Time 2]
0.00/600.00 Secs
0.01 Secs
30.00 Secs
A148 [Decel Time 2]
0.00/600.00 Secs
0.01 Secs
30.00 Secs
A149 [S Curve %]
0/100%
1%
20%
A150 [PID Trim Hi]
0.0/320.0 Hz
0.1 Hz
60.0 Hz
A151 [PID Trim Lo]
0.0/320.0 Hz
0.1 Hz
0.0 Hz
A152 [PID Ref Sel]
0/8
0 = “PID Disabled”
1 = “PID Setpoint”
2 = “Analog In 1”
3 = “Analog In 2”
4 = “Comm Port”
5 = “Setpnt, Trim”
6 = “A-In 1, Trim”
7 = “A-In 2, Trim”
8 = “Comm, Trim”
0
A153 [PID Feedback Sel]
0/2
0 = “Analog In 1”
1 = “Analog In 2”
2 = “Comm Port”
0
A154 [PID Prop Gain]
0.00/99.99
0.01
1.00
A155 [PID Integ Time]
0.0/999.9 Secs
0.1 Secs
2.0 Secs
A156 [PID Diff Rate]
0.00/99.99 (1/Secs)
0.01 (1/Secs)
0.00 (1/Secs)
A157 [PID Setpoint]
0.0/100.0%
0.1%
0.0%
A158 [PID Deadband]
0.0/10.0%
0.1%
0.0%
A159 [PID Preload]
0.0/320.0 Hz
0.1 Hz
0.0%
A160 [Process Factor]
0.1/999.9
0.1
30.0
A163 [Auto Rstrt Tries]
0/9
1
0
A164 [Auto Rstrt Delay]
0.0/160.0 Secs
0.1 Secs
1.0 Secs
A165 [Start At PowerUp]
0/1
0 = “Disabled”
1 = “Enabled”
0
A166 [Reverse Disable]
0/1
0 = “Rev Enabled”
1 = “Rev Disabled”
1
A167 [Flying Start En]
0/1
0 = “Disabled”
1 = “Enabled”
0
A168 [PWM Frequency]
2.0/8.0, 10.0 kHz
0.1 kHz
4.0 kHz
A169 [PWM Mode]
0/1
0 = “Space Vector”
1 = “2-Phase”
1
A170 [Boost Select]
0/15
Settings in % of base voltage.
4
Only active when A125 [Torque Perf Mode] is
set to 0 “V/Hz”.
0 = “Custom V/Hz”
Variable Torque
Constant Torque
1 = “30.0, VT”
5 = “0.0, no IR”
10 = “10.0, CT”
2 = “35.0, VT”
6 = “0.0”
11 = “12.5, CT”
3 = “40.0, VT”
7 = “2.5, CT”
12 = “15.0, CT”
4 = “45.0, VT”
8 = “5.0, CT”
13 = “17.5, CT”
9 = “7.5, CT”
14 = “20.0, CT”
15 = “Kepco”
A171 [Start Boost]
0.0/25.0%
1.1%
2.5%
Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to “0”.
A172 [Break Voltage]
0.0/100.0%
0.1%
25.0%
Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to “0”.
A173 [Break Frequency]
0.0/320.0 Hz
0.1 Hz
15.0 Hz
Only active when A084 [Boost Select] and A125 [Torque Perf Mode] are set to “0”.
A174 [Maximum Voltage]
20/Rated Volts
1 VAC
Rated Volts
A175 [Slip Hertz @ FLA]
0.0/10.0 Hz
0.1 Hz
2.0 Hz
A176 [DC Brake Time]
0.0/99.9 Secs
0.1 Secs
0.0 Secs
A177 [DC Brake Level]
0.0/(Drive Amps
×
1.5) 0.1 Amps
Amps
×
0.05
A178 [DC Brk Time@Strt]
0.0/99.9 Secs
0.1 Secs
0.0 Secs
A179
A180
[Current Limit 1]
[Current Limit 2]
0.0/(Drive Amps
×
1.5) 0.1 Amps
Amps
×
1.1
A181 [Motor OL Select]
0/2
0 = “No Derate”
1 = “Min Derate”
2 = “Max Derate”
0