Control terminal block, Enbl – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual

Page 10

background image

English-10

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

(1)

Important: I/O Terminal 01 is always a coast to stop input
except when P036 [Start Source] is set to option 1 “3-Wire” or
6 “2-W Lvl/Enbl”. In three wire control, I/O Terminal 01 is
controlled by P037 [Stop Mode]. All other stop sources are
controlled by P037 [Stop Mode].
Important: The drive is shipped with a jumper installed
between I/O Terminals 01 and 11. Remove this jumper when
using I/O Terminal 01 as a stop or enable input.

(2)

Two wire control shown. For three wire control use a momentary input

on I/O Terminal 02 to command a

start. If reverse is enabled by A166, use a maintained input

for I/O Terminal 03 to change direction.

(3)

When using an opto output with an inductive load such as a relay, install a recovery diode parallel to the relay as
shown, to prevent damage to the output.

(4)

When the ENBL enable jumper is removed, I/O Terminal 01 will always act as a hardware enable, causing a
coast to stop without software interpretation.

(5)

Most I/O terminals labeled “Common” are not referenced to the safety ground (PE) terminal and are designed to
greatly reduce common mode interference. On Frame D and E drives, Analog Common 1 is referenced to
ground.

(6)

Common for Analog Input 2 (AI2). Electronically isolated from digital I/O and opto output. Not to be used with
Analog Input 1 (AI1), Analog Output 1 (AO1) or Analog Output 2 (AO2). With Analog Input 2, provides one fully
isolated analog input channel.

Control Terminal Block

04

05

06

07

01

02

03

08

09

10

12

13

14

15

16

17

18

19

20

11

Digital Common

Digital Common

Digital Input 1

Digital Input 2

Digital Input 3

Stop/
Function Loss

(1)(4)

Start/Run FWD

(2)

Direction/Run REV

Digital Input 4

Opto Common

R1

R2

R3

#1 Relay N.O.

#1 Relay Common

#1 Relay N.C.

+24V DC Source

+10V DC Source

Analog Input 1 (AI1)

Analog Common 1

Analog Output 2 (AO2)

Analog Output 1 (AO1)

Analog Input 2 (AI2)

Analog Common 2

(6)

Opto Output

RS485 Shield

+24V

+10V

R4

R5

R6

#2 Relay N.O.

#2 Relay Common

#2 Relay N.C.

Typical

SNK Wiring

Typical

SRC Wiring

RS485

(DSI)

Enable

(4)

Jumper

30V DC
50mA
Non-inductive

Common

24V

ENBL

(3)

Pot must be
1-10k ohm
2 Watt Min.

SRC

SNK

SNK

SRC

Earth Referenced
Frames D & E

(5)

0-10V

0-20mA

0-10V

0-20mA

0-10V
0-20mA

1 of 7 Digital Input Circuits

10V 20MA

AO1

10V 20MA

AO2

10V 20MA

AI1

10V 20MA

AI2

Isolated

P036 [Start Source]

Stop

I/O Terminal 01 Stop

Keypad

Per P037

Coast

3-Wire

Per P037

Per P037

(4)

2-Wire

Per P037

Coast

RS485 Port

Per P037

Coast