Weidmuller ACT20X User Manual
Page 66
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
66
1066540000/01/12.11
Sensor error detection (programmable)
3.5 mA / 23 mA / none
Current limit
≤ 28 mA
Accuracy
Absolute Accuracy
Temperature Coefficient
General values
≤
0.1 % of span
≤
0.01 % of span / °C
Basic values
≤
16 µA
≤
1.6 µA / °C
Status Relay
Safe Area
Zone 2 Installation
Voltage max.
125 V AC / 110 V
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A
0.5 A AC / 1 A DC
Power max.
62.5 V AC / 32 W
16 VA / 32 W
Power Supply
Supply voltage
19.2…31.2 V DC
Max. consumption (2-channels)
≤ 3.5 W
Fuse
1.25 A / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply
2.6 kV AC / 300 V AC
Input 1 to input 2
1.5 kV AC / 150 V AC
Status relay to supply
1.5 kV AC / 150 V AC
Environmental Specifications
Ambient temperature
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %
Calibration temperature
+20…28 °C
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D)
105.6 x 22.5 x 114.7 mm
Protection degree
IP20
Screw terminal torque