Weidmuller ACT20X User Manual
Page 50
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
50
1066540000/01/12.11
TC Input, Cold Junction Compensation (CJC)
CJC: external with ACT20X-CJC-HTI
(1160640000)
+20…+28 °C ≤
1 °C
-20…+20 °C and +28…+60 °C ≤
1.6 °C
CJC via internal sensor
t = internal temperature – ambient temperature
(2.0 °C + 0.4 °C * t)
Sensor error detection (programmable, only wire
breakage)
ON/OFF
Sensor error current:
when detecting
else
nom. 2 μA
0 μA
Current Input
Measurement range
0…20 mA
Programmable measurement ranges
0…20 and 4…20 mA
Input resistance
nom. 20 Ω + PTC 50 Ω
Sensor error detection:
loop break (only when input is selected as
4…20 mA)
Yes
Voltage Input
Measurement range
0…12 V DC
Programmable measurement ranges
0…1 V / 0.2…1 V / 0…5 V / 1…5 V / 0…10 V /
2…10 V
Input resistance
nom. > 10 MΩ
Current Output
Signal range (span)
0…23 mA
Programmable signal ranges
0…20 mA / 4…20 mA / 20…0 mA / 20…4 mA
Load max.
4 mA / 600 Ω / 12 V DC
Load stability
≤ 0.01 % of span / 100 Ω
Sensor error detection
0 / 3.5 mA / 23 mA / none
NAMUR NE 43, Upscale / Downscale
23 mA / 3.5 mA
Output limitation:
on 4…20 and 20…4 mA signals
on 0…20 and 20…0 mA signals
3.8…20.5 mA
0…20.5 mA
Current limit
≤ 28 mA