Weidmuller ACT20X User Manual
Page 35
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
1066540000/01/12.11
35
Status Relay
Safe Area
Zone 2 Installation
Voltage max.
125 V AC / 110 V
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Power Supply
Supply voltage
19.2…31.2 V DC
Max. consumption (2-channels)
≤ 3.5 W
Fuse
1.25 A / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply
2.6 kV AC / 300 V AC
Output 1 to output 2
1.5 kV AC / 150 V AC
Status relay to supply
1.5 kV AC / 150 V AC
Environmental Specifications
Ambient temperature
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %
Calibration temperature
+20…28 °C
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D)
105.6 x 22.5 x 114.7 mm
Protection degree
IP20
Screw terminal torque
0.5 Nm
Vibration
IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous
IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire
AWG 26…14 / 0.13…2.08 mm²
EMC immunity influence
≤
0.5 % of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst
≤
1 % of span
Signal/Noise ratio
min. 60 dB (0…100 kHz)