Weidmuller ACT20X User Manual
Page 51
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)
1066540000/01/12.11
51
2-wire 4…20 mA Output
Signal range
4…20 mA
Load resistance
≤ (V
supply
– 3.5 V) / 0.023 A [Ω]
Load stability
≤ 0.01 % of span / 100 Ω
Max. external 2-wire supply
3.5…26 V DC
Effect of external 2-wire supply voltage variation
< 0.005 % of span / V
Relay Output
Safe Area
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Relay functions
Setpoint, Window, Sensor error, Power and Off
Hysteresis in % / display counts
0.1…25 % / 1…2999
On and Off delay
0…3600 s
Sensor error detection
Break / Make / Hold
Status Relay
Safe Area
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0,5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Power Supply
Supply voltage
19.2…31.2 V DC
Max. consumption
≤ 3.5 W
Fuse
1.25 A / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply
2.6 kV AC / 300 V AC
Status relay to supply
1.5 kV AC / 150 V AC
Environmental Specifications
Ambient temperature
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %