beautypg.com

2 status/alarm leds, Status/alarm leds – Weidmuller ACT20X User Manual

Page 22

background image

Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)

22

1066540000/01/12.11

7.1.2 Status/Alarm

LEDs

51

CH2

41

54

44

21 22 23 24

ACT20X

PWR

11 12 13 14

CH1

LED 1

LED 2

LED 3

Illustration 7-1: Status/Alarm LEDs

Channel 1

Channel 2

Condition

LED 1

LED 2

Output

LED 3

Output

Status

Relay (NC)

Device

OK

activated

yellow

ON

energized

de-activated

OFF

OFF

energized

Cha

nnel 1

wire short/break

green

flashing

red

flashing

OFF

de-energized

activated

yellow

ON

energized

de-activated

OFF

OFF

energized

Cha

nnel 2

wire short/break

green

flashing

red

flashing

OFF de-energized

No

supply

OFF OFF OFF OFF OFF

de-energized

Device

failure

OFF red OFF red OFF

de-energized

Flashing:

8% ON and 92% OFF

__|¯|_______|¯|_______|¯|_______

Table 7-1: Status/Alarm LEDs