Calibration temperature
+20…28 °C
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D)
105.6 x 22.5 x 114.7 mm
Protection degree
IP20
Screw terminal torque
0.5 Nm
Vibration
IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous
IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire
AWG 26…14 / 0.13…2.08 mm²
EMC immunity influence
≤
0.5 % of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst
≤
1 % of span
Signal/Noise ratio
min. 60 dB (0…100 kHz)
Response time (0…90 %, 100…10 %):
Temperature input, programmable
mA / V input, programmable
1…60 s
0.4…60 s
Default Settings
Input type
Temperature
Connection type
3-wire
Temperature unit
°C
Temperature sensor type
Pt100
Temperature range
0…150 °C
Output current range
0…20 mA
Output current on error
23 mA
Analog output response time (1/10 s)
1 s
Relay Software Parameters / Default Settings
Function SETPOINT
Contact function
Normally Open (NO)
Setpoint
50 °C (input type temperature) / 50 %
Activation direction
Increasing
Hysteresis
1 °C (input type temperature) / 1 %